Description



Technical specifications (Coolator 34)
| Description | Details |
|---|---|
| Model- Type | COOLATOR® – 34 |
| Cabinet Construction | |
| 25 mm Double skin puff panels with extruded hollow Aluminium profile | |
| Air flow Machine Outlet- in CFM/CMH | 20000 / 34000 |
| Area cooled (sq feet) | Upto 4000 Sqft |
| Static pressure in mm of Wg | 40 |
| Type of Blower | Forward/Backward Curve belt driven fan |
| Make of Blower | Nicotra/Blowtech/Kruger |
| Blower motor connected load kW | 9.3 kW |
| Connected Load | 11.5 kW |
| Make of Motor | ABB/CG/Siemens/Havells |
| Blower Motor Specification | IE2, TEFC , 4Pole , Class F insulation, IP55 protection |
| Make of sensible heat exchanger | SENHEX (EVAPOLER) |
| Adiabatic Heat Exchanger | Cellulose Pad , 5mm flute ht , 100 mm thick – Glo-aire/Eco-cool /Munters |
| Filtration | Non-woven washable synthetic Media (Efficiency 90 % Down to 10 Micron) |
| Dimensions L x W x H (mm) | (3600 x 2500 x 3100) ±100 |
| Unit operating Weight in Kg | 2450 |
| Power supply | Three Phase 415V,50Hz |
| Controller | Industrial Grade Single Speed Controller |
| Mode of operation | Three modes of operation -Ventillation,IEC ,IDEC |
| Additional features available on request. | |
| RH Sensor | Available on request |
| Variable frequency drive. | |
| UV unit for tank water |










































Download Brochure