Description | IDECool 25 |
---|
Type | Blow through design |
AHU box construction | 25 mm thick double skin puff panels with extruded aluminium hollow profiles for structural support |
Type of blower | Backward curve DIDW, dynamically balanced |
Make | Nicotra |
Air flow machine outlet – in CFM/CMH | 25000/42500 |
Make of motor | CG/Rotomotive |
Blower motor specifications | IE2, TEFC 4P, Class F insulation, S1 continuous duty, IP55 protection |
Type of drive | V-belt drive 2SPB |
Make of sensible heat exchanger | HMX-DAMA |
Material of adiabatic heat exchanger/make | Treated and impregnated special cellulose material of 100 mm thick, Eco cool/equivalent |
Type/size of filters | Panel filter of 90% efficiency down to 10 microns/610 x 610 x 50 |
Number of filters | 16 |
Recirculating pumps | 2 submersible, 260 W single phase pumps |
Air inlet louvers | Pre-punched louvers made of GI precoated sheets |
Dimensions W x D x H (mm) | 2850 x 4500 x 2800 |
Starter panel (outdoor type) | Body mounted starter panel with all ON/OFF/trip indications; it will work both in upto and manual mode |
Remote control box | Remote box with 30 m cable length, with ON/OFF switch and indications for low water level, blower, and pump trip |
Total power consumption in kW | 13.2 |
Connected load in kW | 17 |